FeaturesSpecs: SENSORSpecs: ALARM HUB

Part Number:
CG-ELS+ SENSOR

Battery Types:
Vented Lead-Acid (VLA) battery

Alarm Leads: 
Active Open, via RJ25 jack connection

Alarm Activation (Temperature): 
Activation when battery case temperature is greater than 35° C ± 2°C or less than 0°C ± 2°C 

Alarm Activation (Electrolyte Level): 
Activation when level is below ± 2 mm of calibrated reference
Response time: 4 minutes

LED Status Indicator: 
Flashing Green (normal state), Flashing Red (alarm state),
Amber (non-calibrated)

Power Input:
12V dc ± 2V dc at 2.5 mA Typical, via RJ25 jack
CG-ELS+ HUB connection

Operating Temperature Range: 
-10 to 65° C

Storage Temperature Range: 
-20 to 70° C

Dimensions: 
2.60” W X 2.60” D x 1.00” H
(66.04 mm W x 66.04 mm D x 25.4 mm H)

Enclosure: 
94V-0 ABS Plastic Housing

Mounting: 
3M Adhesive Tape

Maximum Case Thickness for Level Sensor: 
1/2” (non-opaque)